Omnigrad S TAF11
High temperature TC thermometer

Omnigrad S TAF11
High temperature TC thermometer ©Endress+Hauser
Omnigrad S TAF11
High temperature TC thermometer ©Endress+Hauser

Applicable for steel treatment (annealing), concrete furnaces and primaries

Measuring points with extremely high process temperatures require these special thermometers with ceramic thermowells and thermocouples made from special metals, such as platinum and rhodium. The thermowell made from special materials serves as protection from mechanical and chemical damages in the process and increases the life span of the used sensors. This leads to: Cost savings for maintenance of the measuring point, quality improvements of the products and increased plant safety.

  • Edut

    • Long lifetime by usage of innovative thermowell materials with increased wear and chemical resistance

    • Long term stable measurement due to sensor protection with non-porous materials

    • Flexible product selection by modular design

    • Optimized life cycle costs by...

  • Käyttöalue

    • Applicable for steel treatment (annealing), concrete furnaces and primaries. It contains a single or double TC insert and a ceramic protection tube.

    • Process temperatures: up to +1600 °C (+2912 °F)

Ominaisuudet ja tiedot

Takaisin

Yksityiskohtaiset tiedot

  • Mittausperiaate

    Thermocouple

  • Characteristic / Application

    metric style

    modular temperature assembly

    high temperature probe (furnace)

    incl. single ceramic thermowell

  • Terminal head

    TA20A - aluminium - cover with screws

    TA20D - aluminium - hinged cover high

    TA30A - E+H, aluminium - cover low - w/o. display

    TA30D - E+H, aluminium - cover high

    DIN A - aluminum

  • Thermowell / protection tube

    ceramic protection tube

  • Insert / probe

    ceramic capilarry, rigid

  • Outer diameter protection tube / Insert

    14,0 mm (0,55")

    16,0 mm (0,59")

    17,0 mm (0,68")

    22,0 mm (0,87")

    24,0 mm (0,94")

    26,6 mm (1,05")

  • Max. immersion length on request

    up to 4.000,00 mm (157,48'')

  • Material protection tube/ thermowell

    Ceramic (C610)

    silicon nitride ceramic (SiN)

    sintered silicon carbide (SiC)

  • Process connection

    compression fitting:

    G3/4"

    G1"

    G11/2"

    adjustable Flange

  • Tip shape

    straight

  • Operating temperature range

    Type K:

    -40 C ...1.300 C

    (-40 F ...2.372 F)

    Type J:

    -40 C ...750 C

    (-40 F ...1.382 F)

    Type N:

    -40 C ...1.150 C

    (-40 F ...2102 F)

    Type S:

    0 C ...1.600 C

    (32 F ...2.912 F)

    Type R:

    0 C ...1.600 C

    (32 F ...2.912 F)

    Type B:

    600 C ...1.600 C

    (1.112 F ...2.912 F)

  • Max. process pressure (static)

    at 20 °C: 1 bar (15 psi)

  • Accuracy

    class 2 acc. to IEC 60584

  • Integration head transmitter

    yes (4 … 20 mA; HART; PROFIBUS PA; FOUNDATION FIELDBUS)

  • Certification

    SIL (transmitter only)

Asiakirjat / käsikirjat / ohjelmisto

Tarvikkeet / varaosat

Nro
Tilauskoodi
Erittely